@Random_Seed@bitbang.social An air cleaner with a CADR of 300cfm would hit an ACH of 6 in a 375 square foot room with 8 foot ceilings. The ACH will be even higher in rooms which are smaller than that. A decent shortcut is to aim for a CADR of 1cfm for every 1 square foot of space with 8-10 foot ceilings. Any taller, and you need to upsize. So, a 200 ft² room would need 200cfm, a 325 ft² room would need 325cfm, and so on. That saves you from having to use the calculator website all the time.